#L010143 November 2003
4 Lead Motors
Multiply the specified series motor current by 1.4 to determine the current adjustment potentiometer
value. Four Lead Motors are usually rated with their appropriate series current, as opposed to the Phase
Current, which is the rating for 6 and 8 lead motors.
8 Lead Motors
Series Connection: When configuring the motor windings in series, use the per Phase (or unipolar)
current rating to determine the current setting potentiometer value.
Parallel Connection: When configuring the motor windings in parallel, multiply the per Phase (or unipo-
lar) current rating by 2.0 to determine the current setting potentiometer value.
NOTE: After the current has been determined, according to the motor connections above, use Table 3 to
choose the proper setting for the current setting potentiometer.